1.General
1.1 Electric ratings: rated voltage 3-1 OkV, rated current up to 630A for load break switchgear and 125A for combined switchgear, 50Hz.
1.2 Application: applicable for power distribution, control, and protection on electric equipments as the loop power supply unit or terminal equipment
1.3 Standards: IEC60420
Type DesignationH X G N 15A 12 (F.R)
------------------------------ Combined load break switch and fuse
--------------------------------------------- Rated voltage
-------------------------------------------------------- Design No.
------------------------------------------------------------------ Indoor
----------------------------------------------------------------------------- Fixed type
--------------------------------------------------------------------------------------- Packaged type
------------------------------------------------------------------------------------------------- Loop
Working ConditionsAmbient temperature: -25°C~+40°C Altitude: <1000m
Humidity: daily average ^95%, monthly average <90% Earthquake intensity: ^magnitude 8 Applicable in the places without corrosive and flammable gas Note: Customized products are available on your requirements
Features4.1 8MF material adopted for the switchgear, modular holes available with E=20mm.
4.2 Switch disconnector, vacuum load break switch, earthing switch and the switchgear door reliably interlocked, which could avoid miss operation.
4.3 Both manual and automatic operation are available.
4.4 There is lead sealed pin at the door of measurement chamber and meter chamber.
4.5 Prompt tripping could be realized to protect the equipments.
4.6 The design facilitate the operation at the front panel and the switchgear could be installed along side the wall.
4.7 The switchgear is featured for its complete interlocking functions: the load break switch could be operated to the making status when the switchgear door is closed and locked and the earthing switch to the making position. The earthing switch could make or break when the load break switch is at disconnect position. When the earthing switch is at making status, input the insulation clapboard to its position, the switchgear door then, could be opened. The vacuum arc-extinguishing chamber and fuse are reliably connected. So as the fuse & switchgear door and insulation clapboard & the switchgear door.
Main Technical ParametersNo. | Items | Unit | Data | |
1 Rated voltage | kV | 12 | ||
2 | Rated current | Load break switchgear | A | 630 |
Combined switchgear | 125 | |||
3 | Rated short-circuit breaking current | kA | 31.5 | |
4 | Rated active on-load breaking current | A | 630 | |
5 | Rated short-time withstands current | kA | 20 | |
6 | Rated withstands current (peak ) | kA | 50 | |
7 | Rated industrial frequency voltage withstands inter-phase, to the earth and to the breaking point | kV | 42/48 | |
8 | Thundering withstands voltage inter-phase, to the earth and to the breaking point | kV | 75/85 | |
9 | Mechanical life | Time | 10000 | |
10 | Rated take-over current | A | 3150 | |
11 | Operating mode | Manual or automatic | ||
12 | Protection degree | IP2X |